Data Sheet for Product
Table Of Contents
12
Siemens
A6V10807602_en
--
_h
Smart Infrastructure
2021
-
07
-
16
Inputs
Connections to multifunctional inputs X1 - M - X2
Passive temperature sensors
- Cable length max. (copper cable section)
- NTC type
Room temperature range
Outdoor temperature range
- Ni type
Room temperature range
Outdoor temperature range
- Pt type
Room temperature range
Outdoor temperature range
90 m (1.5 mm
2
wire), 70 m (1 mm
2
wire)
60 m (0.75 mm
2
wire), 40 m (0.5 mm
2
wire)
NTC10K at 25 °C
0…50 °C
-50…80 °C
Ni1000 at 0 °C
0…50 °C
-50…80 °C
Pt1000_375/Pt1000_385 at 0 °C
0…50 °C
-50…80 °C
Active DC 0 V ...10 V sensors
- Room temperature range (default)
- Outdoor temperature range (default)
- Humidity range (default)
Min./max. configurable via parameters
0…50 °C
-50…80 °C
0…100%
Digital contacts
- Operating action
- Contact sensing
- Parallel connection
- Input function
Selectable NO/NC
DC 14…40 V, 8 mA (typ.)
Max. 20 thermostats per switch
Selectable
Outputs
Switching capacity of relay
Voltage Q11, Q12, Q14
Current, min max resistive (inductive)
Potential free, AC 24…230 V
5 mA...5(2) A
Voltage Q21, Q22, Q24
Current, min max resistive (inductive)
Potential free, AC 24…230 V
5 mA...5(2) A
Note: Connecting different voltages on Q1x and Q2x is allowed (double insulation).
NOTICE
Remove wired bridge L-Q11 when loads work with voltages other than AC 230 V.