User Manual
Operating the thermostat on the device
Advanced settings
6
33 |
58
Siemens
A6V10877569_en
--
_
d
Building Technologies
201
9
-
01
-
08
No.
Application
settings
Descriptions
Factory
settings
Range Dependencies
29.
Humidify
(no fan)
min. ON
time
The minimum working
time of a standalone
humidifier. This
minimum limitation
protects the humidifier
from being destroyed
by frequent
switchovers.
3 min 0…60 min
You’ve
configured the
thermostat
output as
Humidifier (no
fan) in
Changing
system setup
[➙ 36].
30.
Humidify
(no fan)
min. OFF
time
The minimum OFF
time of a standalone
humidifier. This
minimum limitation
protects the humidifier
from being destroyed
by frequent
switchovers.
3 min 0…60 min
31.
Dehum. (no
fan) min.
ON time
The minimum working
time of a standalone
dehumidifier. This
minimum limitation
protects the
dehumidifier from
being destroyed by
frequent switchovers.
3 min 0…60 min
You’ve
configured the
thermostat
output as
Dehumidifier
(no fan) in
Changing
system setup
[➙ 36].
32.
Dehum. (no
fan) min.
OFF time
The minimum OFF
time of a standalone
dehumidifier. This
minimum limitation
protects the
dehumidifier from
being destroyed by
frequent switchovers.
3 min 0…60 min
33.
DHW min.
ON time
The minimum working
time of the domestic
hot water boiler. This
minimum limitation
protects the boiler
from being destroyed
by frequent
switchovers.
3 min 0…60 min
You’ve
configured the
thermostat
output as
Domestic hot
water boiler in
Changing
system setup
[➙ 36].
34.
DHW min.
OFF time
The minimum OFF
time of the domestic
hot water boiler. This
minimum limitation
protects the boiler
from being destroyed
by frequent
switchovers.
3 min 0…60 min
Minimum switchover time
adjustment