User Manual

Operating the thermostat on the device
Advanced settings
6
32 | 58
Siemens
A6V10877569_en
--
_
d
Building Technologies
201
-
01
-
08
No.
Application
settings
Descriptions
Factory
settings
Range Dependencies
24.
Pump/valve
kick cycle
A circle kicked in to
turn on a constantly
idle pump or valve for
a minimum period of
time to protect the
pump or valve from
being locked up. You
can set the kick-in
time interval by
yourself; however, the
minimum time period
the pump or valve is
switched ON depends
on what heating
controllers setting
you’ve selected.
500 h 1…8760 h
Application
setting No. 38;
This function
displays only if
you select the
equipment type
as one of the
following in
Changing
system setup
[ 36]:
Radiator with
valve,
Radiator with
pump, Floor
heating with
valve or Floor
heating with
pump.
25.
Room
presence
detector
Allows switching to
Comfort automatically
if an unoccupied room
is detected to be
occupied when a
scheduled Unoccupied
mode is running.
Active N/A N/A
No.
Application
settings
Descriptions
Factory
settings
Range Dependencies
26.
Built-in
temp.
sensor adj.
Temperature offset
value for the built-in
room temperature
sensor.
0 K -5…5 K
Valid only if the
built-in
temperature
sensor is used
to measure the
temperature.
27.
X1 temp.
sensor adj.
Temperature offset
value for the room
temperature sensor
connected in terminal
X1.
0 K -5…5 K
Valid only if an
external room
temperature
sensor is
connected
using X1.
28.
X2 temp.
sensor adj.
Temperature offset
value for the room
temperature sensor
connected in terminal
X2.
0 K -5…5 K
Valid only if an
external room
temperature
sensor is
connected
using X2.
Functions
Temperature offsets