Operating the thermostat on the device
Advanced settings
6
A6V11562455_en
--_a
31 | 60
No.
Application
settings
Descriptions
Factory
settings
Range
Dependencies
20. Rel.room
dehmdf.setpoint
for comfort
The
dehumidification
setpoint for
Comfort
. This
setpoint must be
lower than the
dehumidification
setpoint for
protection.
60 % RH
0…100 % RH
Displays only if
you’ve
configured the
output as
Dehumidifier
(no fan)
.
21. Rel.room
dehmdf.setpoint
for economy
The
dehumidification
setpoint for
Economy
. This
setpoint must be
lower than the
dehumidification
setpoint for
protection.
60 % RH
0…100 % RH
22. Rel.room
dehmdf.setpoint
for unoccupied
The
dehumidification
setpoint for
Unoccupied
.
This setpoint
must be lower
than the
dehumidification
setpoint for
protection.
70 % RH
0…100 % RH
23. Rel.room
dehmdf.setpoint
for protection
The
dehumidification
setpoint to
maintain when
you switch the
thermostat to
OFF
under >
Operating mode
.
This setpoint
must be lower
than the
dehumidification
setpoint for
protection.
70 % RH
0…100 % RH This setting
displays only if
you’ve
configured the
output as
Dehumidifier
(no fan)
.
This setpoint is
valid only if
you keep the
default
Protection
option for
Application
setting No. 35.
NOTE: Dehumidification control works with a PID algorithm. The algorithm
continuously monitors the difference between the humidity setpoint for
dehumidification and the measured relative air humidity in the room and switches
the dehumidifier ON and OFF to keep the room humidity below the setpoint. The
dehumidifier cannot manually be switched on and off. Changes to the setpoint
impact dehumidification control, thereby verifying functionality.
Dehumidification setpoints