User Manual
Operating the thermostat on the device
Advanced settings
6
A6V11562455_en
--_a
29 | 60
No.
Application
settings
Descriptions
Factory
settings
Range
Dependencies
11. Comfort
heating
setpoint
The default heating
setpoint for
Comfort
defined in a schedule.
This setpoint must be
higher than that for
protection.
21 °C 0…50 °C N/A
12. Economy
heating
setpoint
The default heating
setpoint for
Economy
defined in a schedule.
This setpoint must be
higher than that for
protection.
19 °C 0…50 °C N/A
13.
Unoccupied
heating
setpoint
The default heating
setpoint for
Unoccupied
mode.
This setpoint must be
higher than that for
protection.
15 °C 0…50 °C N/A
14. Protection
heating
setpoint
The default minimum
heating setpoint to
maintain when you
switch the thermostat
to
OFF
under >
Operating mode
.
12 °C 0…50 °C This setpoint is
valid only if you
keep the
default
Protection
option for
Application
setting No. 35.
15.
Max.
heating
setpoint
The default maximum
heating setpoint if the
thermostat is not
switched to
OFF. If it is
OFF
, the maximum
heating setpoint is
then the heating
protection setpoint.
35 °C 0…50 °C
The heating
protection
setpoint is valid
only if you
keep the
default
Protection
option for
Application
setting No. 35.