User Manual
9
Siemens Datasheet A6V10954420_en--_f
Smart Infrastructure 2020-10-29
The transmitter is located in a plastic housing. Two buttons are visible on the rear when
removing the baseplate.
OVERRIDE
Override allows for temporarily overriding the active value from the sender. Override
responds differently depending on the radio connection (normal or fault).
Example A: Normal connection between sender and receiver
Press the OVERRIDE button to overwrite the value for ca. 14 minutes. The value then
returns to the setpoint.
Example B: Faulty connection between sender and receiver
Press the OVERRIDE button to permanently override the value. The value returns to the
setpoint after the connection between sender and receiver works again.
RF LED
RF state RF LED
Power up (first 5 seconds) Flash RED
Power up (after 5 seconds) RED
Press OVERRIDE switch Flash RED + ORANGE (amber)
(4 seconds)
Learning period No LED
Software reset RED
RF receive GREEN
No RF within last 25 minutes RED
Manual override
(RF receive)
Flash ORANGE
Relay LED
Relay state Relay LED
From OUT to ON (first 5 seconds) Flash ORANGE
ON ORANGE
From ON to OFF (after 5 seconds) Flash ORANGE
OFF OFF