User Manual
10
Siemens Datasheet A6V10954420_en--_f
Smart Infrastructure 2020-10-29
Notes
Mounting
When mounting the transmitter, attach the baseplate first. You need to mount the transmitter
on a flat wall. (For details, refer to the separate mounting instructions A6V10974424.)
The transmitter comes with a fold-out stand and may be used as a “mobile” device.
Mounting the receiver does not require a baseplate. Connect the electrical connections first
and then fit and secure the receiver in compliance with local regulations. (For details, refer to
the separate mounting instructions A6V10974424.)
If the reference room contains thermostatic radiator valves, set them to their fully open
position.
For commissioning, refer to the operating instructions A6V101035990.
Communication of RDJ100RF/SET (transmitter and receiver) is bonded ex factory.
● The devices are suitable for wall mounting.
● Recommended height: 1.5 m above the floor.
● Do not mount the devices in recesses, shelves, behind curtains or doors, or above or
near heat sources.
● Avoid direct solar radiation and drafts.
● Seal the conduit box or the installation tube if any, as air currents can affect sensor
readings.
● Adhere to allowed ambient conditions.
Change of batteries
If the battery symbol appears, the batteries are almost empty and must be replaced.
Reset
Simultaneously press the TEST and LEARN buttons on the rear of the transmitter to reset it.
Simultaneously press the OVERRIDE and LEARN buttons to reset the receiver. This resets
all individual settings to their default values.
Maintenance
The transmitter and receiver are maintenance-free except for the transmitter battery.