Wireless room thermostat with 24-hour time switch and LCD RDJ100RF/SET Programmable, for heating systems ● ● ● ● ● ● ● ● A6V10954420_en--_f 2020-10-29 2-position or PID control to switch on/off heating systems Operating modes: Automatic, Comfort, Energy saving, and Frost protection 24-hour time switch Service interval reminder Large LCD display Minimum and maximum setpoint limitation RDJ100RF, transmitter, battery powered RCR100/433, receiver, mains powered Smart Infrastructure
Use The device comprises with 1 x RDJ100RF (transmitter) and RCR100/433 (receiver), is used to control the room temperature in heating systems.
Control behaviour (P01) The factory setting for control is “PID slow”, ideal for most heating systems.
Operating modes The device has the following modes: Automatic, Comfort, Energy saving and Frost protection. Move the operating mode slider to the respective position to select another operating mode. Automatic mode Automatic mode is active when symbol is displayed. The device operates as the selected 24-hour time program. Comfort mode Comfort mode is active when symbol is displayed.
Parameter setting mode 1. Press LEARN on the rear for 5 seconds until “P01” appears. 2. Press advance button, the parameter value on the second line flashes and is ready for adjustment. 3. Adjust the parameter using setting knob. 4. Press advance button once to confirm the setting. 5. Rotate the setting knob clockwise to next parameter and repeat steps 2 to 4. 6. Exit parameter setting mode by rotating the setting knob clockwise to “End” and pressing advance button once.
The service interval reminder can be enabled and reset by a service professional. Equipment combinations Description Product number Data sheet *) Electrothermal actuator (for radiator valves) STA23.. 4884 Electrothermal actuator (for small valves 2.5mm) STP23.. 4884 Electromotoric actuator SFA21.. 4863 *) The documents can be downloaded from http://siemens.com/bt/download. Ordering When ordering, specify name and product number, e.g. room temperature controller RDJ100RF/SET.
RDJ100RF (Transmitter) Elements 1 2 Functions Room temperature display in °C The transmitter controls to the adjusted comfort temperature setpoint 3 The transmitter controls to the adjusted energy saving temperature setpoint 4 The transmitter controls to the fixed frost protection temperature setpoint 5 6 7 8 Setpoint temporarily overridden until the next switching time Indicates low battery power; replace batteries Indicates a heat request Time of day (00:00...
9 Indicates first switch-on/off time 10 Indicates second switch-on/off time 11 Time setting position 12 First switch-on time 13 First switch-off time 14 Second switch-on time 15 Second switch-off time 16 Comfort temperature setting 17 Energy saving temperature setting 18 RUN position 19 Program slider 20 Advance button (override / presence button) 21 Temperature setting knob 22 Battery compartment 23 Operating mode slider 24 RF TEST indicates RF signal test 25 Indicates that
The transmitter is located in a plastic housing. Two buttons are visible on the rear when removing the baseplate. OVERRIDE Override allows for temporarily overriding the active value from the sender. Override responds differently depending on the radio connection (normal or fault). Example A: Normal connection between sender and receiver Press the OVERRIDE button to overwrite the value for ca. 14 minutes. The value then returns to the setpoint.
Notes Mounting When mounting the transmitter, attach the baseplate first. You need to mount the transmitter on a flat wall. (For details, refer to the separate mounting instructions A6V10974424.) The transmitter comes with a fold-out stand and may be used as a “mobile” device. Mounting the receiver does not require a baseplate. Connect the electrical connections first and then fit and secure the receiver in compliance with local regulations.
Disposal The device is considered an electronic device for disposal in accordance with the European Guidelines and may not be disposed of as domestic garbage. ● Dispose of the device through channels provided for this purpose. ● Comply with all local and currently applicable laws and regulations. ● Dispose of empty batteries in designated collection points.
Technical data Power supply Operating voltage DC 3 V (2 x 1.5 V AA alkaline batteries) Battery life >1 year (with AA alkaline batteries) Radio frequency Frequency band ISM 433 MHZ Maximum radio-frequency power 4.
Standards, directives and approvals Pollution degree 2 Degree of protection of housing IP20 Environmental compatibility The product environmental declaration (A6V101123361 *) contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal). *) The documents can be downloaded from http://siemens.com/bt/download.
Switching outputs (LX, L1, L2) Contact life at AC 250 V At 5 A res. 1 x 105 cycles (Guide value) Insulating strength Between relay contacts and coil AC 5,000 V Between relay contacts (same pole) AC 1,000 V Electrical connections Connections terminals (via baseplate) For solid wires For stranded wires Screw terminals 2 x 1.5 mm2 1 x 2.5 mm2(min. 0.5 mm2 ) Environmental conditions Operation Climatic conditions Temperature Humidity IEC 60 721-3 Class 3K3 0…+45 °C <85% r.h.
Connection diagram L Live, AC 230 V Lx Live, AC 24…250 V L1 N.O. contact, AC 24…250 V / 8 (3) A L2 N.C.
Application examples Wireless room temperature controller with receiver control of a gas-fired wall-hung boiler Wireless room temperature controller with receiver control of atmospheric gas burner Wireless room temperature controller with receiver control of a heating circuit pump (pre-control by manual mixing valve) F1 Thermal reset limit thermostat F2 Safety limit thermostat M1 Circulating pump N1 Room temperature controller RDJ100RF (Transmitter) N2 RCR100/433 (Receiver) Y1 3-port valve wit
Dimensions [mm] Room temperature controller Room temperature controller mounting plate 17 Siemens Smart Infrastructure Datasheet A6V10954420_en--_f 2020-10-29
Room temperature receiver with mounting plate Product history Index Date ≥C June 2018 ● Z, A March 1) Changes Add new function min/max temperature limitation, selectable control behavior, parameter settings and service interval reminder. First release. 2017 1) Product index can be found next to the production date on the rear of the device "YYMMDDX". Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58 724 2424 www.siemens.