User Manual
11
Siemens Datasheet A6V10954415_en--_f
Smart Infrastructure 2020-10-29
WARNING
No internal fuse
External preliminary protection with max. C 10 A circuit breaker in the supply line required
under all circumstances.
Operational data
PID control:
Minimum switch on/off time
Minimum period time
Slow
4 min
12 min
Fast
2 min
6 min
Setpoint setting range
Factory setting comfort setpoint
Factory setting for energy saving mode
5…30 °C (Comfort mode)
5…30 °C (Energy saving mode)
5 °C (Frost Protection, fixed value)
20 °C
10 °C
Resolution of
settings and
displays
Temperature
setpoint
0.5 °C
Display of actual
temperature value
0.5 °C
Electrical connections
Connections terminals (via baseplate)
For solid wires
For stranded wires
Screw terminals
2 x 1.5 mm
2
1 x 2.5 mm
2
(min. 0.5 mm
2
)
Environmental conditions
Operation
Climatic conditions
Temperature
Humidity
IEC 60721-3-3
Class 3K5
0…+40 °C
<90% r.h.
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
IEC 60721-3-2
Class 2K3
-25…+60 °C
<95% r.h.
Class 2M2
Storage
Climatic conditions
Temperature
Humidity
IEC 60721-3-1
Class 1K3
-10…+60 °C
<90% r.h.
Standards, directives and approvals
EU conformity (CE) A6V101123363 *)
RCM conformity A6V11161600 *)
Safety class II as per EN 60730-1