User Manual
4
Siemens Datasheet A6V10954418_en--_g
Smart Infrastructure 2020-11-19
Commissioning notes
Parameter list
Parameter Description Factory setting Setting range Remark
P01 Control behavior PID slow (4) 0 = 2P, 1.0 K
1 = 2P, 0.5 K
2 = PID fast
4 = PID slow
P02
Maximum
temperature
range
30 °C P03…30 °C
Limit of comfort
and economy
setpoint
P03
Minimum
temperature
range
5 °C 5 °C…P02
Limit of comfort
and economy
setpoint
End
Exit parameter
setting
Parameter setting
The parameter setting remains in non-volatile memory and is not erased when the battery is
removed. The reset function on the rear of the thermostat reloads the factory settings.
Parameter setting mode
1. Press LEARN on the rear for 5 seconds until “P01”
appears.
2. Press LEARN again and, the parameter value on the
second line flashes and is ready for adjustment.
3. Adjust the parameter using setting knob.
4. Press LEARN once to confirm the setting.
5. Rotate the setting knob clockwise to next parameter and
repeat steps 2 to 4.
6. Exit parameter setting mode by rotating the setting knob
clockwise to “End” and pressing LEARN once.
Note: The thermostat automatically exits parameter setting mode one minute after the last
action.