Recalibrate the temperature sensor if the room temperature displayed on the
thermostat does not match the room temperature measured (after min. 1 hour of
operation). To do this, change parameter P05
We recommend to review the setpoints and setpoint ranges (parameters
P08…P12) and change them as needed to achieve maximum comfort and save
energy
The programming mode helps identify the thermostat in the KNX network during
commissioning.
Press left and right buttons simultaneously for 6 seconds to activate
programming mode, which is indicated on the display with "PrO
g
".
Programming mode remains active until thermostat identification is complete.
Use ETS3 Professional to assign the KNX group addresses of the thermostat's
communication objects.
Each device has a unique KNX serial number at the rear.
An additional sticker with the same KNX serial number is enclosed in the
packaging box. This sticker is intended for installers for documentation purposes.
Calibrate sensor
Setpoint and range
limitation
Programming mode
Assign KNX group
addresses