Technical data

61 / 78
Siemens RDG400KN Basic documentation CE1P3192en
Building Technologies Functions 20 Jul 2010
Parameter
Name Factory setting Range
Communications
P81 Device address 1) 255 1…255
P82 Geographical zone (apartment) 2) --- ---, 1...126
P83 Geographical zone (room) 2) 1 ---, 1...63
P84 Heat distr zone heating coil --- ---, 1...31
P85 Refrig distr zone cooling coil --- ---, 1...31
P86 Heat distr zone heating surface --- ---, 1...31
P87 Air distribution zone --- ---, 1...31
P88 Transformation Precomfort 0 0 = Economy
1 = Comfort
P46, P47: Setting to 2-position or 3-position is made with DIP switches 4 and 5
1) Physical address = Area.Line.DeviceAddress. Factory setting for Area = 0, Line = 2.
Can be changed by special management service e.g. from line coupler or via ACS commissioning tool.
2) Type = geographical zone A.R.S. In RDG sub zone = fixed value 1
Parameter
Name Range
Diagnostics & test
d01 Application number
0 = --- (No application)
1 = Single duct
2 = Single duct with electric heater
3 = Single duct with radiator
4 = Single duct with H/C coil
d02 X1 state 0 = Not activated (for DI)
1 = Activated (DI)
0…49 °C = Current temp. value (for AI)
00
= H/C Input shorted
100
= H/C Input open
d04 D1 state 0 = Not activated (for DI)
1 = Activated (DI)
00
= H/C Input shorted
100
= H/C Input open
d05 Test mode for checking the Y1/Y2 actuator's running
direction 3)
"---" = no signal on outputs Y1 and Y2
OPE = output Y1 forced opening
CLO = output Y2 forced closing
d07 Software version Ux.xx is displayed
3) This parameter can only be quit when the setting is back at “---”.
Press the left button to escape.
Note: