Technical data
33 / 78
Siemens RDG400KN Basic documentation CE1P3192en
Building Technologies Functions 20 Jul 2010
3.6.5 Single-duct with electric heater
General rule: In case of insufficient air flow, the thermostat cannot protect the
electrical heater against overtemperature. Therefore the electric heater MUST
feature a separate safety device (thermal cutout).
On single-duct applications with electrical heater, the thermostat controls a valve
plus an auxiliary electrical heater. Parameter P01 is not available.
The output signal for the air flow can be limited to a minimum and maximum value
if required using parameters P63 and P64. With application " Single-duct with
electric heater", the min. value of P63 is overridden, so that the air flow never drops
below 10 % while the electric heater is ON.
The air flow starts to rise depending on the acquired room temperature, the current
supply air temperature (if available) and the setpoint.
The electrical heater receives an ON command when the acquired room
temperature drops below setpoint (= setpoint for electrical heater).
Remote enabling / disabling of the electric heater is possible via input X1 or D1 for
tariff regulations, energy savings, etc.
Input X1 or D1 must be commissioned accordingly (parameters P38, P42). See
section 3.8 “Multifunctional input”.
The ele
ctric heater can also be enabled / disabled via bus.
If “Enable electric heater” input is used via bus, then the function must not be
assigned to a local input X1 or D1.
On start-up of the controller and if the primary controller sends the information that
the primary fan is off, the thermostat disables the electric heater, see section
3.10.9.
T
o avoid overheating of an electric heater when switched off, the air flow signal of
Vmin must be maintained for a preset "fan overrun time" (P54, factory setting
60sec).
In conjunction with a Synco primary controller it will be assured that the primary fan
keeps running during the fan overrun time.
See also section 3.10.10.
Cau
tion
Electrical heating, active
in cooling mode
Digital input “Enable
electrical heater”
KNX
R
Enable electric heater
Note
"Fan overrun time"