Technical data

28 / 78
Siemens RDG400KN Basic documentation CE1P3192en
Building Technologies Functions 20 Jul 2010
3.6 Control sequences
3.6.1 Sequences overview (setting via parameter P01)
The mode of the control sequence can be set via parameter P01. Depending on
selected application it will have influences either on the air sequence or water
sequence.
In all application the changeover of the air sequence can be done via supply air
temperature sent by the primary controller.
The available sequences depend on the application:
Parameter P01 = 0 P01 = 1 P01 = 2 P01 = 3
Sequence
T °C
T °C
T °C
T °C
T
c/o signal on
X1 / X2 / D1
c/o signal
via bus
Supply air temp.
via bus
Available
for basic
application:
Heating Cooling Manually select
heating or
cooling
sequence
Automatic
heating /
cooling
changeover
Single duct
1)
1)
Single duct & el
heater
- - - -
1)
Single duct &
radiator
- - - -
1)
Single duct &
heating / cooling
coil
2)
2)
1)
1) Changeover air
2) Changeover water (heating / cooling coil)
For the relation between setpoints and sequences, see section 3.6.8.
Application Parameter P01 Influences the...
Single duct
Air sequence
Single duct & el
heater
--
Single duct &
radiator
--
Single duct &
heating / cooling
coil
Water sequence
Notes:
Air sequence vs. water
sequence