Technical data
18 / 78
Siemens RDG400KN Basic documentation CE1P3192en
Building Technologies Functions 20 Jul 2010
Function if no time schedule is received via bus
User profile for operating mode
(selected via P02)
Operating
mode when
activating
function
Function Operating
mode during
function
Operating mode
at the end of
function
Comfort Extension Comfort Protection
Comfort Absence Protection Comfort
P02 = 1
Protection Not available - -
Comfort Extension Comfort Economy
Comfort Absence Economy Comfort
Economy Extension Comfort Economy
Economy Absence Economy Comfort
P02 = 2
Protection Not available - -
Function with time schedule via bus
User profile for operating mode
(selected via P02)
Operating
mode when
activating
function
Function Operating
mode during
function
Operating mode
at the end of
function
Auto Extension Comfort Auto
Auto Absence Protection Auto
Comfort Extension Comfort Auto
Comfort Absence Protection Auto
P02 = 1
Protection Not available - -
Economy Extension Comfort Auto
Economy Absence Economy Auto
P02 = 2
(
)
Protection Not available - -