Technical data

3 / 14
Siemens RDG400KN Room thermostat with KNX communications CE1N3192en
Building Technologies 01 Jun 2010
Applications
The thermostat supports the following applications, which can be configured using
the DIP switches at the rear of the unit or a commissioning tool.
DIP switches 1...3 need to be set to OFF (remote configuration, factory setting) to
select an application via commissioning tool.
Application DIP switches
Remote configuration
via commissioning tool (factory setting)
Synco ACS
ETS3 professional (planned)
1
ON
23
OFF
45
Single-duct
DC 0…10 V damper actuator (P47 = 0)
3-position damper actuator (P47 = 1)
3192S07
B1
T
M
V
M
V
Y
V
1 2 3 4 5
ON
OFF
Single-duct with electric heater
DC 0…10 V damper actuator and ON/OFF,
PWM or 3-position electric heater (P47 = 0)
3-position damper actuator and
DC 0…10 V electric heater (P47 = 1)
3192S08
YE
B1
T
M
V
M
V
Y
V
1 2 3 4 5
ON
OFF
Single-duct and radiator / floor heating
DC 0…10 V damper actuator and ON/OFF,
PWM or 3-position radiator (P47 = 0)
3-position damper actuator and
DC 0…10 V radiator (P47 = 1)
3192S09
MV MV
YV
YR
B1
T
1 2 3 4 5
ON
OFF
Single-duct heating and cooling coil
DC 0…10 V damper actuator and ON/OFF,
PWM or 3-position heating and cooling
(P47 = 0)
3-position damper actuator and
DC 0…10 V heating and cooling
(P47 = 1)
3192S11
(B1)
T
(B1)
M
V
M
V
Y
V
Y1
T
1 2 3 4 5
ON
OFF
Use P47 to change damper output from DC 0...10 V (factory setting) to 3-position
Use P46 to change valve output from ON/OFF (factory setting) to PWM
Use DIP switch 5 to change valve output from ON/OFF to 3-position
Note