Technical data

CE1N3192en
01 Jun 2010
Building Technologies
s
3
192
Room thermostat with
KNX communications
RDG400KN
For VAV heating and cooling systems
KNX bus communications (S-mode and LTE mode)
Backlit display
PI / P control
Output for VAV box / damper: DC 0…10 V / 3-position
Output for heating / cooling coil: ON/OFF, PWM or 3-pos / DC 0..10V
Output signal inversion as an option (DC 0...10 V DC 10...0 V)
2 multifunctional inputs for keycard contact, external sensor, etc
Operating modes: Comfort, Economy and Protection
Control depending on the room or the return air temperature
Supply fan optimization: Input DC 0...10 V for damper position feedback
Automatic or manual heating / cooling changeover
Minimum and maximum limitation of room temperature setpoint
Minimum and maximum limitation of air flow signal
Adjustable commissioning and control parameters
Commissioning with Synco ACS700, ETS3 Professional or via local HMI
Integration into Synco
Integration into DESIGO via group addressing (ETS3) or via individual
addressing
Integration into third-party system via group addressing (ETS3)
Operating voltage AC 24 V