Functions
Control sequences
4
68 | 170
A6V11545892_en--_b
#
Application
mode
Description
Control sequence
enabled
0
Auto
The thermostat automatically
changes over between heating
and cooling.
Heating, cooling or both
1
Heat
The thermostat only allows for
heating.
Heating only
2
Morning warm-up
If "Morning warm-up" is
received, the room is heated
up as fast as possible (as
needed). The thermostat only
allows for heating.
Heating only
3
Cool
The thermostat only allows for
cooling.
Cooling only
4
Night purge
Not supported by fan coil
applications.
N/A (= Auto)
5
Pre-cool
If "Pre-cool" is received, the
room is cooled down as fast
as possible (as needed). The
thermostat only allows for
cooling.
Cooling only
6
Off
Thermostat does not control
outputs, that is, all outputs go
to off or 0%.
Neither heating nor
cooling
8
Emergency heat
The thermostat heats as much
as possible. The thermostat
allows only heating.
Heating only
9
Fan only
All control outputs are set to
0% and only the fan is set to
high speed.
The function is terminated by
any operation on the
thermostat.
Run fan at high speed
Application mode
ACS
Heating or cooling