Basic Documentation
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-stage heating and cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.12.1 S-Mode
- 4.12.2 Master/slave configuration in KNX S-Mode
- 4.12.3 LTE-Mode
- 4.12.4 Zone addressing in LTE-Mode (with Synco)
- 4.12.5 Master/slave configuration in LTE-Mode
- 4.12.6 Example of heating and cooling demand zones
- 4.12.7 Send heartbeat and receive timeout
- 4.12.8 Startup
- 4.12.9 Heating and cooling demand
- 4.12.10 Fault and alarms function on KNX
- 4.13 Communication objects
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index
Functions
Additional functions
4
A6V11545892_en--_b
55 | 170
– Fan speed: The manual fan is below or equal to the auto fan speed value
– Operating mode: The manual mode is lower or equal to the scheduler
mode
● Red leaf: The settings exceed the preset energy-efficiency range
P110 configures the green leaf function:
● 0 = Disabled (OFF)
● 1 = Green and red dimmed down
● 2 = Green dimmed down / red fixed
● 3 = Green and red fixed
Energy-efficient setting
Exceed the preset energy-efficient
range
Touch to reset user setting
Set TIME
WARNING
Time synchronization via bus
Time of day and date information are received from a Synco controller with time
master function (RMB, RMB, OWZ, etc) or any other KNX device e.g. GPS clock
if the corresponding communication object is bound.
The scheduler function must be enabled before setting the time of day:
● Press once and then turn the rotary knob or press continuously to
select programming mode TIME.
● Press once and then turn the rotary knob to select the time format.
● If 12H is selected, press once and then turn the rotary knob to select AM or
PM.
● Press once and enter the hour setting.
● The hour value flashes and can be changed by turning the rotary knob.
● Press once to confirm the adjusted value and enter the minutes setting.
Repeat the steps as for the hour.
Set Time / date