Basic Documentation
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-stage heating and cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.12.1 S-Mode
- 4.12.2 Master/slave configuration in KNX S-Mode
- 4.12.3 LTE-Mode
- 4.12.4 Zone addressing in LTE-Mode (with Synco)
- 4.12.5 Master/slave configuration in LTE-Mode
- 4.12.6 Example of heating and cooling demand zones
- 4.12.7 Send heartbeat and receive timeout
- 4.12.8 Startup
- 4.12.9 Heating and cooling demand
- 4.12.10 Fault and alarms function on KNX
- 4.13 Communication objects
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index
Functions
Additional functions
4
48 | 170
A6V11545892_en--_b
Time schedule via
Bus
Presence detector behavior
Comfort mode
When hotel guests leave their rooms (room is unoccupied),
the operating mode changes to Economy. The buttons are
locked and symbol is displayed.
Economy mode
● When hotel guests leave their rooms (room is
unoccupied), the operating mode changes to Economy.
The buttons are locked and symbol is displayed.
● When the room is occupied, the operating mode
changes to the previous operating mode.
Protection mode
Presence detection has no influence on the operating
mode.
Not available
● When hotel guests leave their rooms (room is
unoccupied), the operating mode changes to Economy.
The buttons are locked and symbol is displayed.
● When a room is occupied, the operating mode changes
to the previous operating mode.
● When the schedule changes to Economy but the presence detector is still
active, the operating mode remains in Comfort mode until the presence
detector becomes inactive.
● The contact (e.g., a card reader) can be connected to multifunctional input X1,
X2 or U1 (set P150, P153 or P155 to 10) or occupancy is sent via bus from a
KNX presence detector (only one input source must be used, either local input
X1/X2/U1 or KNX bus).
4.6.3 Output functions
The changeover sensor ensures changeover between heating and cooling mode
based on the acquired water temperature. We recommend activating the Purge
function (P251) with 2-port valves. This function ensures correct acquisition of the
medium temperature even if the 2-port valve is closed for an extended period of
time. The valve is opened for 1 to 5 minutes (adjustable) at 2-hour intervals during
off hours.
The function is valid for outputs PWM, On/Off, On/Off 3-wire, DC, 3-position and all
applications.
Limit the On/Off switching cycle to protect HVAC equipment, e.g., compressor and
reduce wear and tear. The minimum output on-time and off-time for the On/Off
control output can be adjusted from 1 to 20 minutes via P212 and P213. The
factory setting is 1 minute.
Readjusting the setpoint or heating/cooling mode changeover immediately results
in calculation of the output state; the outputs may not hold the minimum 1-minute
On/Off time.
If P212 or P213 is set to greater than 1 minute, the minimum On/Off time for the
control output is maintained as set, even if the setpoint or changeover mode is
readjusted.
For 2-pipe and 2-stage applications with different equipment, e.g., fan coil units
and radiant heating/cooling panels, it is possible to invert the sequence of the
equipment to optimize energy use, when the thermostat changes the sequence
from heating to cooling (P001 = 2 or 3).
Under factory settings, the 1
st
stage in heating (YHC1) is also the 1
st
stage in
cooling.
Notes
Purge function (P251)
Minimum output On/Off
time (P212, P213)
Swap outputs for 2-pipe
and 2-stage applications
(P254)