Functions
Additional functions
4
A6V11545892_en--_b
47 | 170
P151 (X1), P154 (X2) or P156 (U1) = 0
(default, normally open)
P151 (X1), P154 (X2) or P156 (U1) = 1
(Normally close)
Contact open heating mode
Contact open cooling mode
Contact closed cooling mode
Contact closed heating mode
Time schedule via
bus
Presence detector behavior
Comfort mode
When the presence detector is activated or deactivated, the
operating mode remains in Comfort.
Economy mode
When the presence detector is activated, the operating
mode changes to Comfort.
When the presence detector is deactivated, the
operating mode changes to Economy (Auto).
Protection mode
Presence detection has no influence on the operating
mode.
Not available
When the presence detector is activated, the operating
mode changes to Comfort.
When the presence detector is deactivated, the
operating mode changes to previous operating mode.
Manual heating/cooling
changeover (P001)
External/return air
temperature sensor
(P150, P153, P155)
Standard presence mode
(Input: P150 / P153 / P155
= 10)
Hotel presence mode
(Input: P150 / P153 / P155
= 13)