Basic Documentation

Table Of Contents
Functions
Application overview
4
42 | 170
A6V11545892_en--_b
Applications, DIP setting, control outputs
Chilled/heated
ceiling
Chilled/
heated ceiling
and electric
heater
Chilled/heated
ceiling and
radiator/floor
heating
Using RDG200KN, RDG260KN
Using RDG200KN, RDG260KN
Using RDG200KN, RDG260KN
2-stage
chilled/heated
ceiling
Chilled ceiling
and radiator
Chilled and
heated ceiling
control with 6-
port ball valve
Using RDG200KN, RDG260KN
Using RDG200KN, RDG260KN
Using RDG260KN
Chilled and
heated ceiling
control with
PICV and 6-port
ball valve as
changeover
2-stage chilled
and heated
ceiling
YHC Heating/cooling valve actuator
YH Heating valve actuator
YC Cooling valve actuator
YE Electric heater
D3 Dewpoint sensor
M1 1-speed or 3-speed fan, DC 0…10 V
fan
B1 Return air temperature sensor or
external room temperature sensor (optional)
B2 Changeover sensor (optional)
Using RDG260KN
Using RDG200KN, RDG260KN
Product No.
Control outputs
RDG200KN
On/Off, PWM, 3-position
RDG260KN
On/Off, DC 0…10 V