Basic Documentation
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-stage heating and cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.12.1 S-Mode
- 4.12.2 Master/slave configuration in KNX S-Mode
- 4.12.3 LTE-Mode
- 4.12.4 Zone addressing in LTE-Mode (with Synco)
- 4.12.5 Master/slave configuration in LTE-Mode
- 4.12.6 Example of heating and cooling demand zones
- 4.12.7 Send heartbeat and receive timeout
- 4.12.8 Startup
- 4.12.9 Heating and cooling demand
- 4.12.10 Fault and alarms function on KNX
- 4.13 Communication objects
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index
Functions
Room temperature setpoints
4
38 | 170
A6V11545892_en--_b
is not too great. If the outside temperature is higher than 26 °C and 6 K above the
Comfort cooling setpoint, the related setpoint is shifted and kept 6 K below the
outside temperature. This function can be enabled or disabled via P255.
The current setpoint (used by the thermostat for temperature control) is available
on the bus for use in the central control unit.
The Comfort setpoint w (e.g., customer setting on the display) and the current
setpoint w2 (used by the thermostat for temperature control, but not displayed) are
handled differently depending on the selected application and setting.
Both the Comfort setpoint w and current setpoint w2 have the same value.
Heating mode
Cooling mode
The Comfort setpoint w (value selectable by e.g., rotary knob) is in the middle of
the dead zone (P055). The current setpoints w2.. (used by the thermostat for
temperature control) are at the boundaries of the dead zone.
w2h = Comfort setpoint (w) – ½ dead zone (X
dz
)
w2c = Comfort setpoint (w) + ½ dead zone (X
dz
)
Cooling setpoint tracking
depending on outside
temperature (P255)
Current setpoint
Clarification concerning
current setpoint in Comfort
mode
2-pipe with P010 = 1 or
4-pipe with P010 = 1 and
P001 = 3
4-pipe with P010 = 1










