Basic Documentation
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-stage heating and cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.12.1 S-Mode
- 4.12.2 Master/slave configuration in KNX S-Mode
- 4.12.3 LTE-Mode
- 4.12.4 Zone addressing in LTE-Mode (with Synco)
- 4.12.5 Master/slave configuration in LTE-Mode
- 4.12.6 Example of heating and cooling demand zones
- 4.12.7 Send heartbeat and receive timeout
- 4.12.8 Startup
- 4.12.9 Heating and cooling demand
- 4.12.10 Fault and alarms function on KNX
- 4.13 Communication objects
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index
Functions
Operating modes
4
A6V11545892_en--_b
31 | 170
During the extended presence/absence periods, symbol is displayed.
Function if no time schedule is received via bus
User profile for
operating mode
(selected via P002)
Operatin
g mode
when
activating
function
Mode
button
Function
Operating
mode
during
function
Operating
mode at
the end of
function
P002 = 1:
Comfort
Extension
Comfort
Protection
Comfort
Absence
Protection
Comfort
P002 = 2:
Comfort
or
Economy
Extension
Comfort
Economy
Comfort
or
Economy
Absence
Economy
Comfort
P002 = 3:
Comfort
Extension
Comfort
Protection
hospitality
Comfort
Absence
Protection
hospitality
Comfort
Extension/absence is not available in Protection mode.
Function with time schedule via bus
User profile for
operating mode
(selected via P002)
Operating
mode when
activating
function
Mode
butto
n
Function
Operating
mode
during
function
Operati
ng
mode at
the end
of
function
P002 = 1:
Auto
Extension
Comfort
Auto
Comfort
Extension
Comfort
Auto
Auto
Absence
Protection
Auto
Comfort
Absence
Protection
Auto
P002 = 2:
Auto,
Comfort or
Economy
Extension
Comfort
Auto
Auto,
Comfort or
Economy
Absence
Economy
Auto
P002 = 3:
Auto
Extension
Comfort
Auto
Comfort
Extension
Comfort
Auto
Auto
Absence
Protection
hospitality
Auto
Comfort
Absence
Protection
hospitality
Auto
Extension/absence is not available in Protection mode.
Note
Note