Basic Documentation
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-stage heating and cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.12.1 S-Mode
- 4.12.2 Master/slave configuration in KNX S-Mode
- 4.12.3 LTE-Mode
- 4.12.4 Zone addressing in LTE-Mode (with Synco)
- 4.12.5 Master/slave configuration in LTE-Mode
- 4.12.6 Example of heating and cooling demand zones
- 4.12.7 Send heartbeat and receive timeout
- 4.12.8 Startup
- 4.12.9 Heating and cooling demand
- 4.12.10 Fault and alarms function on KNX
- 4.13 Communication objects
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index
Functions
Temperature control
4
24 | 170
A6V11545892_en--_b
4 Functions
4.1 Temperature control
Setting control parameters (P001 etc. mentioned throughout the document), see
Control parameters [➙ 126].
The thermostat acquires the room temperature via built-in sensor, external room
temperature sensor (LG-Ni1000 or NTC 3k), external return air temperature sensor
(LG-Ni1000 or NTC 3k) or via KNX (S-Mode or LTE-Mode), and maintains the
setpoint by delivering actuator control commands to heating equipment, cooling
equipment, or both. The following control outputs are available:
● On/Off control (2-position)
● Modulating PI/P control with PWM output
● Modulating PI/P control with 3-position control output
● Modulating PI/P control with DC 0...10 V control output
The switching differential is 1 K for heating/cooling mode (On/Off valve: P051 and
P053).
The proportional band is 2 K for heating mode and 1 K for cooling mode (DC, PWM
and 3-pos valves: P050 and P052).
The integral action time for modulating PI control is adjustable via P057 (heating)
and P058 (cooling) (factory setting: 45 minutes).
The display shows the acquired room temperature or the Comfort setpoint,
selectable via P008. The factory setting displays the current room temperature.
Configure P004 to display the room temperature or setpoint in °F or °C as needed.
When P002 = 3 and P009 = 1, switch the unit between °C and °F via operating
mode button, and the symbol is displayed as . When the unit is changed, P004
is updated accordingly. This function is only available with LCD module V1 and
later.
When P008 = 1, the Comfort setpoint is always displayed even when the operating
mode changes.
The acquired room temperature (internal or external sensor) is available as
information on the bus.
RDG2..KN can also acquire the room temperature via KNX.
● With automatic changeover or continuous heating/cooling, symbols
indicate that the system is currently in heating or cooling.
● With manual changeover (P001 = 3), symbols indicate that the system
currently is in heating or cooling mode and symbols indicate that the
system is currently in heating or cooling. Thus, the symbols are displayed even
when the thermostat operates in the neutral zone.
Concurrent display of the current room temperature setpoint or current room
temperature in °C and °F is available (P009 = 1).
The outside temperature displays on the thermostat (P009 = 2). This temperature
value has only informational character.
In LTE-Mode, the outside temperature can only be received on outside
temperature zone 31.
In S-Mode, the corresponding communication object must be bound to a KNX
sensor device.
General note:
Parameters
Temperature control
Display
Note
Room temperature
Concurrent display of °C
and °F
Outside temperature via
bus