Basic Documentation

Table Of Contents
Connection
Application examples
6
158 | 170
A6V11545892_en--_b
Commissioning
Outputs used
Fan P350 = 6 (Cooling
and 2
nd
stage heating)
Valve P201 = 5 (panel)
Valve P203 = 5 (fan coil
unit)
Swap P254 = 1
M1 DC 0...10 V fan
(2
nd
stage)
V1 DC valve panel
V2 DC valve fan coil
unit
See Technical data [ 160] for min. and
max. ratings
RDG260KN
Example 2:
Swap and fan in the 2
nd
stage