Commissioning
Outputs used
Fan P351 = 3
(or DIP6 = OFF)
Valve P201 = 5
Relay function P402 = 1
(Protection mode)
M1 DC 0...10 V fan
V1 DC valve
L3
*)
Fan coil
K Relay
*)
Release contact
See Technical data [ 160] for min. and
max. ratings
RDG260KN
Commissioning
Outputs used
Fan P351 = 3
(or DIP6 = OFF)
Valve P201/P203 = 5
Relay function P401 = 3
(heating pump)
Relay function P402 = 4
(cooling pump)
M1 DC 0...10 V
fan
V1, V2 DC valve
L2
*)
Heating pump
L3
*)
Cooling pump
K Relay
*)
Release contact
See Technical data [ 160] for min. and
max. ratings
RDG260KN
Example 1:
Switching off the fan coil
unit
Example 2:
Switching on pumps