Basic Documentation

Table Of Contents
Supported KNX tools
ACS tool
5
144 | 170
A6V11545892_en--_b
Plant type
Application
configuration
Application
configuration
2-pipe
2-pipe fan coil unit
Control sequence: No impact
(P001 = any)
Fan operation: Enabled (P350 <> 0)
Radiator
Control sequence: Heating only (P001 = 0)
Fan operation: Disabled (P350 = 0)
Chilled/heated ceiling
Control sequence: Changeover
Fan operation: Disabled (P350 = 0)
Chilled ceiling
Control sequence: Cooling only (P001 = 1)
Fan operation: Disabled (P350 = 0)
2-pipe with
electric
heater
2-pipe fan coil unit with electric heater
Control sequence: No impact
(P001 = any)
Fan operation: Enabled (P350 <> 0)
Single-stage with electric heater
Control sequence: No impact (P001 = any)
Fan operation: Disabled (P350 = 0)
2-pipe with
radiator
2-pipe fan coil unit with radiator
Control sequence: No impact
(P001 = any)
Fan operation: Enabled (P350 <> 0)
Single-stage with radiator
Control sequence: No impact (P001 = any)
Fan operation: Disabled (P350 = 0)
4-pipe
4-pipe fan coil unit
Control sequence: Not auto c/o
(P001 <> 3)
Fan operation: Enabled (P350 <> 0)
Chilled ceiling with radiator
Control sequence: No impact (P001 = any)
Fan operation: Disabled (P350 = 0)