Basic Documentation
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-stage heating and cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.12.1 S-Mode
- 4.12.2 Master/slave configuration in KNX S-Mode
- 4.12.3 LTE-Mode
- 4.12.4 Zone addressing in LTE-Mode (with Synco)
- 4.12.5 Master/slave configuration in LTE-Mode
- 4.12.6 Example of heating and cooling demand zones
- 4.12.7 Send heartbeat and receive timeout
- 4.12.8 Startup
- 4.12.9 Heating and cooling demand
- 4.12.10 Fault and alarms function on KNX
- 4.13 Communication objects
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index
Functions
Control parameters
4
134 | 170
A6V11545892_en--_b
Parameter
Name
Factory
setting
Range
RDG200KN
RDG260KN
Dependencies
Expert level
Relay functions
P400
9)
Output Q1 function
0
0 = No function
1 = Switch OFF in Protection
2 = Switch ON in Heat/Cool demand
3 = Switch ON in Heat demand
4 = Switch ON in Cool demand
5 = Heating sequence active
6 = Cooling sequence active
7 = External dehumidifier control
10)
8 = External humidifier control
10)
✓
✓
✓
✓
✓
✓
✓
M
M
✓
✓
✓
✓
✓
✓
✓
M
M
P350, P351,
P258
P401
9)
Output Q2 function
P402
Output Q3 function
Controller
P450
10)
Control strategy
0
0 = Temperature (T)
1 = Temperature (T) + Relative humidity
(r.h.)
M
M
P258
P451
10)
Humidity control strategy
2
1 = With setpoint shift
2 = With setpoint shift + external
equipment (humid / dehum)
M
M
P450, P258
P461
10)
T setpoint shift (humidity)
3 K
-3…3 K
M
M
P450, P258
Side Features
P500
NFC
ON
ON = Enabled
OFF = Disabled
✓
✓
‒
P501
10)
Service filter
---
--- (OFF), 100…9900 h
M
M
P350, P258
P502
Password
OFF
ON = Enabled
OFF = Disabled
✓
✓
‒
P503
Password
000
000…999
✓
✓
‒
P505
Reset parameter setting
OFF
OFF = Disabled
ON = Reload start
✓
✓
‒
System
P898
Area address
0
0…15
✓
✓
‒
P899
Line address
2
0…15
✓
✓
‒
P900
Device address 3)
255
1…255
✓
✓
‒
P901
Geographical zone (apartment) 4)
---
---(0), 1...126
✓
✓
‒
P902
Geographical zone (room) 3)
1
---(0), 1...63
✓
✓
‒
P903
Heat distr zone heating coil
---
---(0), 1...31
✓
✓
‒
P904
Refrig distr zone cooling coil
P905
Heat distr zone heating surface
P910
Transformation Precomfort
0
0 = Economy
10)
1 = Comfort
M
✓
M
✓
P258
Note: Appl means application.
1)
When P201/P203 = 1/3/5, P204/P205 = 3/5, P057 & P058 are visible.
2)
When P150, P153 or P155 = 2 and P001 = 2, P059 & P060 are visible.
3)
When P002 ≠ 2, P102 is visible.
4)
Only available for application 2-pipe/2-stage.
5)
When P201 = 3, P206 is visible; P203 = 3, P207 is visible; P204 = 3, P208 is visible; P205 = 3, P209 is
visible.
6)
When P201 = 1, P214 is visible; P203 = 1, P215 is visible.
7)
When
"H/C changeover" function on X1, X2, U1 is selected, P251 is visible.
8)
When
"External temperature limit (AI)" on X1, X2, U1 is selected, P252 is visible.
9)
When application is 4-pipe with 6-port ball valve as changeover and PICV, P400 & P401 are invisible.
10)
If P258 = 0 (Slave), the parameter values are not visible.
11)
Only available for applications 2-pipe, 2-pipe with electric heater and 2-pipe with radiator.
12)
If P258 = 0 (Slave), the parameter values are visible.