Basic Documentation
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-stage heating and cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.12.1 S-Mode
- 4.12.2 Master/slave configuration in KNX S-Mode
- 4.12.3 LTE-Mode
- 4.12.4 Zone addressing in LTE-Mode (with Synco)
- 4.12.5 Master/slave configuration in LTE-Mode
- 4.12.6 Example of heating and cooling demand zones
- 4.12.7 Send heartbeat and receive timeout
- 4.12.8 Startup
- 4.12.9 Heating and cooling demand
- 4.12.10 Fault and alarms function on KNX
- 4.13 Communication objects
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index
Functions
Control parameters
4
130 | 170
A6V11545892_en--_b
Parameter
Name
Factory
setting
Range
RDG200KN
RDG260KN
Dependencies
Service level
P027
3)
Electric heater when cooling
ON
ON: Enabled
OFF: Disabled
✓
✓
Appl
P028
4)
Keypad
0
0 = Unlocked
1 = Auto lock
2 = Manual lock
3 = Auto lock the operating mode
4 = Auto lock the Setpoint shift
5 = Auto lock fan speed
6 = Auto lock operating mode, setpoint shift
7 = Auto lock operating mode, fan speed
8 = Auto lock fan speed, setpoint shift
9 = Auto lock scheduler
10 = Auto lock operating mode, scheduler
11 = Auto lock scheduler, fan speed
12 = Auto lock operating mode, scheduler, fan
speed
13 = Auto lock scheduler, setpoint shift
14 = Auto lock operating mode, scheduler,
setpoint shift
15 = Auto lock scheduler, fan speed, setpoint
shift
M
M
P258
P029
Fan: Dead zone Comfort mode
2)
0
0 = Fan disable
1 = Low speed (Heating and Cooling)
2 = Low speed (Cooling only)
3 = Fan disable Auto & Manual
4 = Low speed Auto & Manual
5 = Low speed Auto & Manual Cooling
✓
✓
P350
P030
Buzzer function
ON
ON = Enabled
OFF = Disabled
✓
✓
‒
P031
Language
1
1 = English
2 = Francais (French)
3 = Deutsch (German)
4 = Italiano (Italian)
5 = Espanol (Spanish)
6 = Nederlands (Dutch)
7 = Turkce (Turkish)
8 = Cesky (Czech)
9 = Suomi (Finnish)
10 = Polski (Polish)
11 = Magyar (Hungarian)
12 = Slovenski (Slovak)
13 = (Limba) Romana (Romanian)
14 = Dansk (Danish)
15 = Norsk (Norwegian)
✓
✓
‒
P032
4)
Room operating mode holidays
0
0 = Economy
1 = Protection
M
M
P005,
P258
Note:
1)
P001 cannot be set to 3 if P002 is set to 3, and vice versa.
2)
If P350 = 0, P003 is disabled. P029 is invisible.
3)
Only available when application is 2-pipe with electric heater
4)