Basic Documentation

Table Of Contents
Functions
Control parameters
4
130 | 170
A6V11545892_en--_b
Parameter
Name
Factory
setting
Range
RDG200KN
RDG260KN
Dependencies
Service level
P027
3)
Electric heater when cooling
ON
ON: Enabled
OFF: Disabled
Appl
P028
4)
Keypad
0
0 = Unlocked
1 = Auto lock
2 = Manual lock
3 = Auto lock the operating mode
4 = Auto lock the Setpoint shift
5 = Auto lock fan speed
6 = Auto lock operating mode, setpoint shift
7 = Auto lock operating mode, fan speed
8 = Auto lock fan speed, setpoint shift
9 = Auto lock scheduler
10 = Auto lock operating mode, scheduler
11 = Auto lock scheduler, fan speed
12 = Auto lock operating mode, scheduler, fan
speed
13 = Auto lock scheduler, setpoint shift
14 = Auto lock operating mode, scheduler,
setpoint shift
15 = Auto lock scheduler, fan speed, setpoint
shift
M
M
P258
P029
Fan: Dead zone Comfort mode
2)
0
0 = Fan disable
1 = Low speed (Heating and Cooling)
2 = Low speed (Cooling only)
3 = Fan disable Auto & Manual
4 = Low speed Auto & Manual
5 = Low speed Auto & Manual Cooling
P350
P030
Buzzer function
ON
ON = Enabled
OFF = Disabled
P031
Language
1
1 = English
2 = Francais (French)
3 = Deutsch (German)
4 = Italiano (Italian)
5 = Espanol (Spanish)
6 = Nederlands (Dutch)
7 = Turkce (Turkish)
8 = Cesky (Czech)
9 = Suomi (Finnish)
10 = Polski (Polish)
11 = Magyar (Hungarian)
12 = Slovenski (Slovak)
13 = (Limba) Romana (Romanian)
14 = Dansk (Danish)
15 = Norsk (Norwegian)
P032
4)
Room operating mode holidays
0
0 = Economy
1 = Protection
M
M
P005,
P258