Basic Documentation

Table Of Contents
Functions
Communication objects
4
124 | 170
A6V11545892_en--_b
Obj
Object name
Function
Type/
length
Flags
Obj
Object name
Function
Type/
length
Flags
93
Room temp:
Current cooling
setpoint (receive)
Temperature
9.001
2 bytes
CWU
96
ChangeOverWate
r status (receive)
Heating: 1
Cooling: 0
1.100
1 bit
CWU
Communication object adjusts the current cooling setpoint
received by the thermostat from bus (see Setting and adjusting
setpoints [ 36]).
The range is 5...40 °C .
S-Mode object needs to be enabled by setting Room temp:
Current setpoint to as group object in ETS.
Water changeover information received via bus.
97
Manual fan
command value
(send)
0...100 %
5.001
1 byte
CRT
Sends the manual fan command value.
94
Room operating
mode: Status
(receive)
Comfort
Economy
Protection
20.102
1 byte
CWU
98
DC fan speed:
Maximum speed
heating
0...100 %
5.001
1 byte
CWU
Actual room operating mode received by the thermostat (Master)
from bus (considering time switch, user selection, window contact,
etc.) This state information is available via one 8-bit enumeration.
DC fan speed for maximum heating output received via bus.
95
ChangeOverWate
r status (send)
Heating: 1
Cooling: 0
1.100
1 bit
CRT
99
DC fan speed:
Maximum speed
cooling
0...100 %
5.001
1 byte
CWU
Sends the water changeover information.
DC fan speed for maximum cooling output received via bus.