Basic Documentation
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-stage heating and cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.12.1 S-Mode
- 4.12.2 Master/slave configuration in KNX S-Mode
- 4.12.3 LTE-Mode
- 4.12.4 Zone addressing in LTE-Mode (with Synco)
- 4.12.5 Master/slave configuration in LTE-Mode
- 4.12.6 Example of heating and cooling demand zones
- 4.12.7 Send heartbeat and receive timeout
- 4.12.8 Startup
- 4.12.9 Heating and cooling demand
- 4.12.10 Fault and alarms function on KNX
- 4.13 Communication objects
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index
Functions
Communication objects
4
A6V11545892_en--_b
117 | 170
The table below shows the error code and default alarm texts.
Priorities
Fault
Thermostat
Fault information on
bus
Display
Error code
Default
fault text
Text
adjustable
1)
-
No fault
---
0
No fault
✓
1
Bus power
supply
2)
BUS
5000
No bus
power
supply
---
2
Device
address error
Addr
6001
>1 id device
address
---
3
Condensation
COND
4930
Condensati
on in the
room
✓
4
External fault
input X1
AL1
9001
Fault input 1
✓
5
External fault
input X2
AL2
9002
Fault input 2
✓
6
External fault
input U1
AL3
9003
Fault input 3
✓
7
Clean filter
reminder
FIL
3911
Dirty filter
✓
1)
Default alarm texts are stored in the thermostat’s non-volatile memory and can
be adjusted using the ACS commissioning tool.
2)
This error is not sent over the bus (because there is no bus, not enough bus
power supply, bus is overloaded or bus signal is distorted).
● Priority order is #1…7
● External faults #4…6: If faults are active, the display shows AL1, AL2, AL3,
alternating. Only the fault with the highest priority is sent over the bus.
A supervisor alarm system may command the thermostat to stop sending faults to
the bus via the communication object "Fault transmission" (disable/enable).
This has no impact on the local display of faults.
After a timeout of 48 hours, the sending of faults is automatically enabled again.
4.13 Communication objects
4.13.1 Overview
Priority of alarms
Fault transmission










