Basic Documentation

Table Of Contents
Functions
KNX communications
4
110 | 170
A6V11545892_en--_b
4
The master/slave binding is set using communication objects, for object details, see Master/slave
communication in KNX S-Mode [ 65].
Binding setting on master
Binding setting on slave
S-Mode objects master
S-Mode objects slave
Setpoint:
90]
[91]
[27]
Room temp: Current cooling setpoint
(send)
Room temp: Current heating setpoint
(send)
Room temp: Comfort setpoint abs (send)
[93]
[92]
[26]
Room temp: Current cooling setpoint
(receive)
Room temp: Current heating setpoint
(receive)
Room temp: Comfort setpoint abs (receive)
Room temperature:
[37]
Built-in room temperature value
[36]
External room temperature value
Room humidity:
[77]
Built-in room relative humidity value
[%r.h.]
[78]
External room relative humidity value [% r.h.]
Operation mode:
[17]
Room operating mode: Status
[94]
Room operating mode: Status (receive)
ChangeOverWater:
[95]
ChangeOverWater status
[96]
ChangeOverWater status
Fan speed:
[97]
[51]
Manual Fan command value (send)
FanStatus
[52]
[50]
Fan command value
FanManual
Master/slave binding via communication objects