Basic Documentation

Table Of Contents
Functions
Handling system faults
4
A6V11545892_en--_b
107 | 170
Fault
Thermostat
Fault information on bus
Display
Error code
Default fault text
Built-in sensor fails
and no external
sensor is
connected
Er1
---
---
EEPROM is
damaged
Er2
---
---
External / remote
sensor error
Er3
101
[N.X1] sensor error
External / remote
sensor error
Er4
102
[N.X2] sensor error
External / remote
sensor error
Er5
103
[N.U1] sensor error
S-Mode
Standard mode; engineering via group addresses.
LTE-Mode
Logical Tag Extended mode, for easy engineering, is used
together with Synco.
Temperature out of range
Fault "Er1, Er2, Er3, Er4,
Er5" on display