Basic Documentation
Table Of Contents
- 1 About this document
- 2 Overview
- 3 Notes
- 4 Functions
- 4.1 Temperature control
- 4.2 Operating modes
- 4.3 Room temperature setpoints
- 4.4 Application overview
- 4.5 Power supply selection for RDG200KN
- 4.6 Additional functions
- 4.7 Control sequences
- 4.7.1 Sequence overview (setting via P001)
- 4.7.2 Application mode
- 4.7.3 2-pipe fan coil unit
- 4.7.4 2-pipe fan coil unit with electric heater
- 4.7.5 2-pipe fan coil unit with radiator or floor heating
- 4.7.6 2-stage heating and cooling
- 4.7.7 4-pipe fan coil unit
- 4.7.8 4-pipe fan coil unit with electric heater
- 4.7.9 Chilled/heated ceiling and radiator applications
- 4.7.10 Compressor applications
- 4.7.11 Applications with external AQR sensor or QMX room operator unit
- 4.7.12 Setpoints and sequences
- 4.8 Control outputs
- 4.9 Fan control
- 4.10 Multifunctional input, digital input
- 4.11 Handling system faults
- 4.12 KNX communications
- 4.12.1 S-Mode
- 4.12.2 Master/slave configuration in KNX S-Mode
- 4.12.3 LTE-Mode
- 4.12.4 Zone addressing in LTE-Mode (with Synco)
- 4.12.5 Master/slave configuration in LTE-Mode
- 4.12.6 Example of heating and cooling demand zones
- 4.12.7 Send heartbeat and receive timeout
- 4.12.8 Startup
- 4.12.9 Heating and cooling demand
- 4.12.10 Fault and alarms function on KNX
- 4.13 Communication objects
- 4.14 Communication objects (LTE-Mode)
- 4.15 Control parameters
- 5 Supported KNX tools
- 6 Connection
- 7 Technical data
- 8 Dimensions
- Index
Functions
Multifunctional input, digital input
4
106 | 170
A6V11545892_en--_b
#
Input function
Description
Type
X1/X2/U1
11
External temperature
limit
The sensor is connected to the pipe and
measures the temperature of the floor heating
water. When the value exceeds the selected limit
(P252), heating is stopped. See also Monitoring
and limiting functions [➙ 51]
AI
12
Coil flow temperature
To avoid cooling flow air in the room, the sensor
measures the coil water temperature and
releases the fan only when the selected minimum
hot water temperature limit is exceeded (P366).
See also Fan control [➙ 103].
To measure the flow temperature of the return
flow delta temperature control
AI
Hotel
presence
detector
13
Hotel presence detector
Hotel presence detector input switches the
operating mode to Economy when the room is
unoccupied and symbol is displayed (buttons
are locked) and returns to previous operating
mode when the room is occupied.
Hotel presence detector is also possible via bus.
In this case, do not assign the function to local
inputs X1, X2 or U1. See also Presence detector
[➙ 47].
DI
14
Coil return temperature
To save energy, the thermostat controls the valve
to adjust flow speed when ΔT between flow and
return temperature value is less than P061 or
P062. See also Monitoring and limiting functions
[➙ 51].
AI
● Control action can be changed from normally open (NO) and normally closed
(NC) via P151, P154 or P156.
● Each input X1, X2 or U1 must be configured with a different function (1…5 &
9…13). Exception: 1, 2 or 3 inputs can be configured as fault (6) or monitor
input (7,8).
● X1 is factory-set to "External sensor" (1), X2 to "Not used" (0), and U1 to
"Window contact" (3).
For more detailed information, see Application overview [➙ 40].
● For inputs X1, X2, or U1, one physical switch can be used for up to 20
thermostats (parallel connection).
● In 4-pipe/2-stage application of RDG260KN, U1 is fixed as DC output (YC2)
and cannot be set as input.
Caution! Do not mix X1/X2 and U1.
● For sensors on inputs X1, X2, or U1, the maximum cable length is 80 m.
Note