Fan control
4
100 | 170
A6V11545892_en--_b
Note: Manual fan settings
do not influence control
signals "Heating" and
"Cooling".
P350 = 4: 2
nd
stage
Fan runs in the 2
nd
stage in heating and cooling (example 1
or 2 when combined with the swap function)
P350 = 5: Heating and 2
nd
stage
cooling
Fan runs in heating mode and in the 2
nd
stage cooling
(example 3)
P350 = 6: Cooling and 2
nd
stage
heating
Fan runs in cooling mode and in the 2
nd
stage heating
P350 = 7: 2
nd
stage cooling only
Fan runs in the 2
nd
stage cooling only and not in heating
mode
P350 = 8: 2
nd
stage heating only
Fan runs in the 2
nd
stage heating only and not in cooling
mode
Heating mode
Cooling mode
Manual operation
DC 0...10 V fan
Note
2 sequences
heating/cooling
Fan in the 2
nd
stage
Example 1