User Manual
Functions
Communication objects (S
-
Mode)
4
96 | 146 A6V11545892_en--_a
Priorities Fault Thermostat Fault information on bus
Display Error code
Default fault
text
Text
adjustable
1)
- No fault --- 0 No fault ✓
1
Bus power
supply
2)
BUS
5000
No bus
power
supply
---
2
Device
address error
Addr
6001
>1 id device
address
---
3 Condensation
COND
4930
Condensati
on in the
room
✓
4
External fault
input X1
AL1
9001 Fault input 1 ✓
5
External fault
input X2
AL2
9002 Fault input 2 ✓
6
External fault
input U1
AL3
9003 Fault input 3 ✓
7
Clean filter
reminder
FIL
3911 Dirty filter ✓
1)
Default alarm texts are stored in the thermostat’s non-volatile memory and can
be adjusted using the ACS commissioning tool.
2)
This error is not sent over the bus (because there is no bus, not enough bus
power supply, bus is overloaded or bus signal is distorted).
● Priority order is #1…7
● External faults #4…6: If faults are active, the display shows AL1, AL2, AL3,
alternating. Only the fault with the highest priority is sent over the bus.
A supervisor alarm system may command the thermostat to stop sending faults to
the bus via the communication object "Fault transmission" (disable/enable).
This has no impact on the local display of faults.
After a timeout of 48 hours, the sending of faults is automatically enabled again.
4.13 Communication objects (S-Mode)
4.13.1 Overview
Priority of alarms
Fault transmission