User Manual

Functions
Fan control
4
84 | 146 A6V11545892_en--_a
Fan speed III = max. fan speed selectable via P359 (heating), P360 (cooling)
Note: Manual fan settings
do not influence control
signals "Heating" and
"Cooling".
When heating with the electric heater only, manual fan speed I is unavailable to
guarantee the necessary minimum air flow for the electric heater and to avoid
overheating of the system.
For heating or cooling with 2 sequences (e.g. heating with a heating coil and an
electric heater, or 2-stage cooling), the fan is always synchronized with the 1
st
stage.
For 2-pipe and 2-stage applications, based on the equipment, the fan may have to
run in the 2-stage only (in the 1
st
stage the fan remains OFF), either in the heating
or cooling sequence.
The following settings are available by selecting the fan control P350 accordingly:
P350 = 4: 2
nd
stage
Fan runs in the 2
nd
stage in heating and cooling (example
1 or 2 when combined with the swap function)
P350 = 5: Heating and 2
nd
stage cooling
Fan runs in heating mode and in the 2
nd
stage cooling
(example 3)
P350 = 6: Cooling and 2
nd
stage heating Fan runs in cooling mode and in the 2
nd
stage heating
P350 = 7: 2
nd
stage Cooling only
Fan runs in the 2
nd
stage cooling only and not in heating
mode
P350 = 8: 2
nd
stage Heating only
Fan runs in the 2
nd
stage heating only and not in cooling
mode
The fan runs only in the 2
nd
stage in the heating and cooling sequence (2-pipe and
2-stage application).
Set both P201 and P203 to 4 or 5 (based on the requested control signal) and set
P350 to 4 (fan in the 2
nd
stage).
Heating mode Cooling mode
Fan in the 2
nd
stage
Note
2 sequences
heating/cooling
Example 1