User Manual

Functions
Control outputs
4
A6V11545892_en--_a 79 | 146
4.8.2 Control output configuration (setting via DIP switches 7/8 or
tool, and P201/P203/P204)
Application Fan Control outputs
Product
no.
DC
0...10 V 3-speed/
1-speed
Mod.
DC 0…10 V
On/Off
(2-pos)
On/Off
(3-wire)
Mod. PWM
(2-pos)
Mod.
3-pos.
RDG…KN
2-pipe 200
260
260
2-pipe with electric
heater
200
260
260
2-pipe with
radiator/floor
heating
200
260
260
2-pipe/2-stage,
cooling or heating
200
260
260
4-pipe 200
260
260
4-pipe with electric
heater
1)
200
260
2)
260
Heating / Cooling
with 6-port valve
260
Heating / Cooling
with 6-port valve as
changeover and
PICV valve
3)
260
1)
Only available for the cooling actuator
2)
Only selectable for electrical heater
3)
Relay outputs for 6-port valve as changeover
Note: On/off (2-pos) on RDG200.. are a triac outputs (max 1A), on RDG260.. are
relay outputs (max 5(4)A)
The type of the control outputs (2- or 3-position) is set via DIP switches 7 and 8.
The patterns of DIP switches 7 and 8 are as follows:
Overview
RDG200KN