User Manual
Functions
Control sequences
4
72 | 146 A6V11545892_en--_a
When control sequences change, the thermostat closes the combi valve and
releases the corresponding relay to operate the ball valve.
A delay of 120 seconds is needed before the combi valves can be operated by the
thermostat.
When the relay to ensure the ball valve is on the right H/C position, the control
signal for the combi valve is released.
When the thermostat is set with control sequence “H/C ceiling with PICV and 6-port
ball valve as changeover”:
● For PICV control, only the Y10 output can be used to control the combi valve.
● For 6-port ball valve as changeover :
– The relay Q1 is energized when “Heating sequence active” (P400 = 5,
fixed, cannot be changed)
– The relay Q2 is energized when “Cooling sequence active” (P401 = 6,
fixed, cannot be changed)
Wiring diagram of the application H/C ceiling with PICV and 6-port ball valve as
changeover is available in Connection diagrams [➙ 126].
4.7.10 Compressor applications
For compressor applications,
● Set the corresponding basic application as per Applications overview [➙ 36].
● Disable the fan (P350) or set the type of fan speed (P351)
● Select the type of control outputs (On/Off, P201, P203, P204)
The following applications are available:
Application for
compressor in DX-type
equipment
Set basic
application
Section Sequences
1-stage compressor 2-pipe
2-pipe fan coil unit
[➙ 57]
H ( \ )
C ( / )
1-stage compressor
with reversing valve
2-pipe
2-pipe fan coil unit
[➙ 57]
H + C ( \ / )
1-stage compressor
and electric heater
(cooling only: disable
electric heater via
P027)
2-pipe with electric
heater
2-pipe fan coil unit
with electric heater
[➙ 58]
El. H + H ( ↯\ \ )
El. H + C ( ↯\ /)
C ( / )
1-stage compressor
for heating and cooling
4-pipe
4-pipe fan coil unit
[➙ 64]
H + C ( \ / )
2-stage compressor
2-stage heating or
cooling
2-pipe/2-stage
heating or cooling
[➙ 62]
H + H ( \ / )
C + C ( / / )
Minimum On/Off time:
Fan operation:
Fan speed:
Control outputs On/Off:
Control outputs DC 0...10 V:
P212/P213 (only with On/Off control outputs)
P350 (0 = disabled, 1 = enabled)
P351 (1 = 1-speed, 2 = 3-speed,
3 = DC 0...10 V)
P201 = 4 (V1) P203 = 4 (V2) (DC 0…10 V fan
only)
P201 = 5 (V1) P203 = 5 (V2)
Control output
Note