4
A6V11545892_en--_a 69 | 146
4.7.9 Chilled/heated ceiling and radiator applications
For chilled/heated ceiling and radiator applications
Set the corresponding basic application see Applications overview [ 36].
Disable the fan (P350)
The following applications are available:
Application for
chilled/heated ceiling,
radiator
Set basic
application
Section Sequences
Chilled/heated ceiling
with changeover
2-pipe
2-pipe fan coil unit
[ 57]
H ( \ )
C ( / )
Chilled/heated ceiling
and electric heater
(cooling only: disable
electric heater via
P027)
2-pipe with electric
heater
2-pipe fan coil unit
with electric heater
[ 58]
El H + H (\ \ )
El H + C ( \ / )
C ( / )
Chilled/heated ceiling
and radiator
2-pipe with radiator
2-pipe fan coil unit
with radiator or
floor heating
[ 60]
H + rad ( \ r\ )
Rad + C ( r\ / )
Chilled ceiling and
radiator
4-pipe
4-pipe fan coil unit
[ 64]
H + C ( \ / )
Chilled/heated ceiling,
2-pipe/2-stage
2-pipe/2-stage
heating or cooling
2-pipe/2-stage
heating or cooling
[ 62]
H + H ( \ \ )
C + C ( / / )
4.7.9.1 Chilled/heated ceiling with 6-port control ball valve
(RDG260KN)
The RDG260KN is able to control a 6-port control ball valve for a chilled and
heated ceiling application.
This application is available when the thermostats are set as 4-pipe with 6-port ball
valve application (DIP4 = ON, see Applications for universal systems [ 38]).
Only one signal DC 0…10V (Y10 output) is used to control the 6-port control ball
valve for cooling and heating.
Principle