User Manual

Functions
Control sequences
4
A6V11545892_en--_a 61 | 146
Heating mode Cooling mode
T[°C] Room temperature
XpH Proportional band "Heating"
(P050)
w Room temperature setpoint
XpC Proportional band "Cooling"
| (P052)
YHC Control command "Valve" or
"Compressor"
XpR Proportional band "Radiator"
(P054)
YR Control command "Radiator" X
dz
Dead zone (P055)
w
D
Setpoint differential (P056)
The diagrams only show the PI thermostat’s proportional part.
For setting sequence and control outputs, see Applications overview [ 36],
Sequence overview (setting via P001) [ 54] and Control outputs [ 75].
Parameter P256 (RDG260KN) sets the heating flow limitation when using a PICV.
See Additional functions [ 41].
Note
Note