User Manual
Functions
C
ontrol sequences
4
54 | 146 A6V11545892_en--_a
For the info about commissioning via Siemens smartphone application PCT Go for
Android, see Commissioning.
4.7 Control sequences
4.7.1 Sequence overview (setting via P001)
The main control sequence (that is, the water coil sequence of the fan coil unit) can
be set via P001.
The following sequences can be activated in the thermostats (with or without
auxiliary heating).
The available sequences depend on the application (selected via DIP switches,
see Applications overview [➙ 36]).
Parameter P001 = 0 P001 = 1 P001 = 2 P001 = 3 P001 = 4
Sequence
Available for basic
application 1):
⇓
Heating Cooling
= heating sequence
for electric
heater/radiator
Automatic
heating/cooling
changeover via
external water
temperature sensor or
remote switch
Manually select
heating or cooling
sequence (using HMI)
Heating and cooling
sequence , that is, 4-
pipe
2-pipe
2-pipe with el. heater
2-pipe with radiator
4-pipe
4-pipe with el. heater
2)
2-pipe/2-stage
heating or cooling
1)
For chilled/heated ceiling and radiator applications, see Chilled/heated ceiling
and radiator applications [➙ 69];
2)
For manual changeover with 4-pipe applications, see 4-pipe fan coil unit [➙ 64].
● 4-pipe manual changeover (P001 = 3) means activating either cooling or
heating outputs
● P001 cannot be configured for applications with 6-port ball valve.
For the relationship between setpoints and sequences, see Setpoints and
sequences [➙ 73].