4
36 | 146 A6V11545892_en--_a
4.4 Applications overview
The RDG2..KN room thermostats support the following applications, which can be
configured using the DIP switches at the rear of the unit or commissioning tool.
Set DIP switches 1…5 to OFF (remote configuration, factory setting) to select an
application via commissioning tool.
Remote configuration, via commissioning tool (factory setting)
● Synco ACS
● ETS
● Commissioning via Siemens smartphone application PCT
Go for Android
ON =
DIP NO.: 1…5
OFF =
DIP NO.: 1…5
RDG200KN RDG260KN
Application
Application
Fan coil fan speed
ON: 3-speed
OFF: DC 0…10 V
Fan coil fan speed
ON: 3-speed
OFF: DC 0…10 V
FCU control outputs #1
ON: 3-position
OFF: 2-position
Control outputs #1
ON: On/Off
OFF: DC 0…10 V
FCU control outputs #2
ON: 3-position
OFF: 2-position
Control outputs #2
ON: On/Off, 6-port valve DC
invert
OFF: DC 0…10 V, 6-port
valve DC invert
Reserve Reserve
Icon Description Icon Description
Heating/cooling
register
Cooling register
Heating register Electric heater
Chilled/heated
ceiling
Chilled ceiling
Heat
pump/compressor
Radiator
Remote configuration