User Manual

Functions
Roo
m temperature setpoints
4
A6V11545892_en--_a 33 | 146
CAUTION
If a
setpoint (Economy or Protection) is set to OFF, the thermostat does not
control the room temperature in the corresponding mode (heating or cooling). In
other words, there is no protective heating or cooling function and thus risk of
frost in heating mode or risk of overtemperature in cooling mode!
The Economy setpoints (P019, P020) are accessible at the Service level; the
Protection setpoints (P100, P101) are accessible at the Expert level.
4.3.2 Setting and adjusting setpoints
Room temperature setpoints can be
set during commissioning
adjusted during runtime
The source can be one of the followings:
The local HMI
A KNX tool
A central control unit
Siemens smartphone application PCT Go for Android
The thermostat stores the setpoints in…
EEPROM in the form of parameters
The runtime memory
The figure below shows the interrelations:
Comfort basic setpoint
Comfort setpoint
Economy heating setpoint
4)
Economy cooling setpoint
4)