User Manual
Functions
Operating modes
4
A6V11545892_en--_a 29 | 146
Window contact
In Room 1, the window is opened briefly, once in the morning and once in the late
afternoon (1). The opening in the morning and afternoon has a direct impact on the
actual room operating mode.
During lunch break (2), the time schedule changes to Precomfort. The mode
remains in Comfort as set by parameter "Transformation Precomfort" (P910 = 1).
Interaction of user operation (operating mode button) and central time schedule
In Room 2, the window is opened briefly, once in the morning and once in the late
afternoon (1).
Only the opening in the morning has a direct impact on the actual room operating
mode.
With the operating mode button, the operating mode can be changed between
OFF and Auto or to temporary Comfort extension.
● During lunch break, the time schedule changes to Precomfort. The mode of the
thermostat changes to Economy as set by parameter "Transformation
Precomfort" (P910 = 0) (6)
● During lunch break, the user changes the operating mode to Comfort
(temporary Comfort extension) by pressing the operating mode button (2)
● At 13:00, the timer is reset due to mode change by the central time schedule
● In the afternoon, the user switches off the thermostat by pressing the operating
mode button (3). At 17:00 the user setting is reset to Economy by the time
schedule
● At 19:30, the user again extends the Comfort mode (4)
Example 1
Example 2