User Manual
Functions
Operating modes
4
28 | 146 A6V11545892_en--_a
User profile for
operating mode
(selected via P002)
Operating
mode
when
activating
function
Mode
button
Function
Operating
mode during
function
Operating
mode at the
end of
function
P002 = 3:
Comfort Extension Comfort
Protection
hospitality
Comfort Absence
Protection
hospitality
Comfort
Extension/absence function is not available in Protection mode.
Function with time schedule via bus
User profile for operating
mode (selected via P002)
Operating
mode
when
activating
function
Mode
button
Function
Operating
mode
during
function
Operatin
g mode
at the
end of
function
P002 = 1:
Auto Extension Comfort Auto
Comfort Extension Comfort Auto
Auto Absence Protection Auto
Comfort Absence Protection Auto
P002 = 2:
Auto,
Comfort
or
Economy
Extension Comfort Auto
Auto,
Comfort
or
Economy
Absence Economy Auto
P002 = 3:
Auto Extension Comfort Auto
Comfort Extension Comfort Auto
Auto Absence
Protection
hospitality
Auto
Comfort Absence
Protection
hospitality
Auto
Extension/absence function is not available in Protection mode.
4.2.2 Communication examples
The following examples show 3 typical applications for a central time schedule in
conjunction with local control of the room operating mode.
The room operating mode in rooms 1…3 of a building is determined by the time
schedule. Window contacts are fitted in all rooms.
The following conditions are specified:
The rooms are used and controlled by the time schedule as follows:
● Night setback from 17:00 to 08:00 (Economy)
● Lunch break from 12:00 to 13:00 (Precomfort)
The substitution (P910) for Precomfort via bus is set on the thermostats as follows:
● Room 1: Comfort (1)
● Room 2: Economy (0)
Note
Note