User Manual
Notes
Operation
3
20 | 146 A6V11545892_en--_a
User action Effect, description
Press left button while "Operating
mode" via bus is Economy
Activate "Extend Comfort mode"
(for details, see Different ways to
influence the operating mode [➙ 27]).
Keep left button pressed and turn rotary
knob clockwise/counter-clockwise
Activate timer "Extend
presence"/"Extend absence" and set
the time (for details, see Different ways
to influence the operating mode [➙ 27].
Press right button >3 seconds Activate/deactivate button lock.
Press right button for fan coil unit Change fan mode.
Turn rotary knob
Adjust the room temperature Comfort
setpoint.
Press left and right buttons
simultaneously for 3 seconds. Release
and within 2 seconds, press the right
button again until P001 is displayed
Enter parameter setting mode "Service
level".
Press left and right button for 3
seconds, release, press left button for 2
seconds until the temperature
disappears, then turn rotary knob
counterclockwise min. ½ revolution
Enter parameter setting mode "Expert
level", diagnostics and test.
Press left and right button
simultaneously for 6 seconds
Enter (KNX) programming mode.
# Symbol Description # Symbol Description
1
Operating mode
selection
2 Fan speed selection
3 Escape 4 Confirm parameters
5 Outside temperature 6
Additional user information,
such as outside
temperature, time of day
from KNX bus, relative
humidity
7
Morning: 12-hour format (via bus), Afternoon: 12-hour format (via
bus)
8 Relative humidity 9
Degrees Celsius or
Fahrenheit
Display