User Manual

Connection
Application examples
6
A6V11545892_en--_a 135 | 146
2-pipe and 2-stage application with radiant heating/cooling panels, the fan only
operates with the fan coil unit:
Heating sequence: 1
st
panel and 2
nd
fan coil unit
Cooling sequence: 1
st
fan coil unit and 2
nd
panel
Commissioning Outputs used
Fan P350 = 6 (Cooling
and 2
nd
stage heating)
Valve P201 = 5 (panel)
Valve P203 = 5 (fan coil
unit)
Swap P254 = 1
M1 DC 0...10 V fan
(2
nd
stage)
V1 DC valve panel
V2 DC valve fan coil
unit
See Technical data [ 137] for min. and max. ratings
RDG260KN
Example 2:
Swap and fan in the 2
nd
stage