User Manual

Connection
Application examples
6
A6V11545892_en--_a 133 | 146
Compressor application, with reversing valve (heating/cooling) and DC 0...10 V
fan:
Commissioning Outputs used
Application 4-pipe
Control output P201 = 4 (On/Off)
Fan P351 = 3
(or DIP6 = OFF)
Relay function Heating/cooling
ON in demand: P401 = 2
Energized mode: Heating P401 = 5
Energized mode: Cooling P401 = 6
M1 DC 0...10 V
fan
V1
*)
Reversing
valve
V2
*)
Compressor
K Relay
*)
Release contact
See Technical data [ 137] for min. and max. ratings
RDG260KN
Example 3:
Compressor and
reversing valve